Powervolt Group GP Standard A00 Series: Everything You Need to Know

admin By admin June 19, 2026

Part of the Powervolt Group Industrial Control Transformers knowledge hub

This article covers the GP Standard A00 Series in depth. For a complete overview of all three Powervolt control transformer series, VA sizing methodology, installation guidance, and certifications, see the full pillar guide.

  Back to: Industrial Control Transformers – Complete Guide

The GP Standard A00 Series is Powervolt Group’s flagship line of industrial control transformers for 220–480 V environments.

The series spans 14 VA ratings – from the compact 25 VA GP0025-A00 used in indicator panels, up to the 2000 VA GP2000-A00 for high-load plant infrastructure – all UL/cUL 5085-2 Listed (File E47299), CE marked, RoHS and REACH compliant, and backed by Powervolt Group’s 10-year warranty. Every unit is manufactured and 100% tested in Addison, Illinois, USA.

Browse & Check Price – All A00 Models In Stock

All 14 GP Standard A00 models are stocked at Powervolt Group’s Addison, Illinois facility. Check live pricing, datasheets, and availability for each part number.

→  Browse GP Standard A00 Series on powervoltgroup.com →

Powervolt Group:  1-888-797-8658 (Toll Free)   |   (630) 628-9999   |   [email protected]

What Defines the A00 Series

The A00 designation identifies GP Standard transformers wound for a 220/440, 230/460, or 240/480 V single primary 110, 115, or 120 V secondary – the dominant voltage pairing in North American industrial control. All 14 models share the same electrical platform:

  • Dual-wound, fully isolated primary-to-secondary – eliminates common-mode noise on sensitive control circuits
  • Class B (130 °C) insulation standard – suitable for standard panel environments up to 40 °C ambient
  • High inrush withstand – secondary voltage held at ≥ 85% rated during inrush (see regulation data table in Section 3)
  • UL/cUL 5085-2 Listed, UL File E47299 – North American compliance out of the box
  • CE marked, RoHS compliant, REACH compliant – ready for international and European projects
  • Exceeds NEMA ST-1, ANSI, NMBTA, JIC, and IEC standards
  • IEC touch-proof (finger-safe) terminal blocks – safe, code-compliant panel wiring
  • Copper coils for excellent thermal characteristics
  • Heavy-gauge steel mounting plate with 4 mounting slots – fits standard panel-mount configurations
  • Optional fuse blocks (CC-class or slow-blow) – fuse block kits available for easy field installation
  • 50/60 Hz dual-rated – North American and international supply frequencies
  • 10-year warranty – backed by Powervolt Group, Addison, Illinois, USA

Need a different voltage pairing – 600 V primary, 240 V secondary, or 575 V supply? See the Industrial Control Transformers pillar guide for Powervolt Group’s full three-series comparison: GP Standard, GP Econoline, and GP Enclosed.

A00 vs GP Econoline – When to Choose Which

The GP Econoline Series offers a lower initial cost but is only available in 300–1500 VA and uses Class F (155 °C) insulation only.

For machinery with frequent start-stop cycles, VA ratings below 300 VA, or applications requiring Class B insulation, specify the GP Standard A00 Series.

The A00 Series uses heavier copper windings and a higher-grade core for superior inrush performance and longer service life.

Browse GP Econoline Series   |   Browse GP Enclosed Series (NEMA 1/4/4X)

All 14 A00 Models at a Glance

Click any part number to go directly to its live product page on powervoltgroup.com for datasheet download, pricing, and stock status. All models carry UL File E47299 and are RoHS and REACH compliant.

VAPart No.PrimaryTypical LoadApplication
25 VAGP0025-A00220/440, 230/460, 240/480 VPilot lights, small control loadsIndicator panels, annunciators
50 VAGP0050-A00220/440, 230/460, 240/480 VSingle contactor + pilot lightsSimple motor starters
75 VAGP0075-A00220/440, 230/460, 240/480 VMulti-contactor, light dutyLight-duty starter panels
100 VAGP0100-A00220/440, 230/460, 240/480 VPLC + I/O modulesProgrammable control panels
150 VAGP0150-A00220/440, 230/460, 240/480 VMulti-relay + HMI displaysMid-complexity automation
200 VAGP0200-A00220/440, 230/460, 240/480 VMotor starters, panel boardsCombination starter panels
250 VAGP0250-A00220/440, 230/460, 240/480 VMultiple solenoids + relaysVFD + PLC + I/O panels
300 VAGP0300-A00220/440, 230/460, 240/480 VLarge panel boardsMulti-axis control panels
350 VAGP0350-A00220/440, 230/460, 240/480 VHeavy relay logic panelsComplex relay logic systems
500 VAGP0500-A00220/440, 230/460, 240/480 VMachine tool control circuitsCNC and machining centres
750 VAGP0750-A00220/440, 230/460, 240/480 VAutomation systems, conveyorsFull MCC bucket applications
1000 VAGP1000-A00220/440, 230/460, 240/480 VLarge machine control panelsSCADA + dual PLC systems
1500 VAGP1500-A00220/440, 230/460, 240/480 VHeavy industrial automationRobot cells, stamping lines
2000 VAGP2000-A00220/440, 230/460, 240/480 VHigh-load plant infrastructureCentral automation rooms

Shared Specifications – All 14 A00 Models

SpecificationValue
Primary voltage220/440, 230/460, 240/480 V AC (series parallel terminal block)
Secondary voltage110, 115, 120 V AC
Frequency50/60 Hz dual-rated
Insulation classClass B (130 °C)
Inrush withstandSee Powervolt regulation data table in Section 3 — ≥ 85% secondary voltage at rated inrush
CertificationsUL/cUL 5085-2 Listed (File E47299), CE marked, RoHS, REACH
Standards metExceeds NEMA ST-1, ANSI, NMBTA, JIC, IEC
ConstructionOpen-frame, copper windings, silicon-steel laminated core
TerminalsIEC touch-proof (finger-safe) terminal blocks
Fuse optionsOptional CC-class or slow-blow fuse blocks; fuse block kits available
Ambient temp.−20 °C to +40 °C operating; derate above 40 °C per Powervolt thermal curve
EnclosureNone — mount inside a NEMA-rated control panel
Warranty10 years — Powervolt Group Inc., Addison, Illinois, USA
Made inUSA — 100% manufactured and tested in Addison, Illinois

How to Size an A00 Transformer for Your Panel

The full sizing methodology – including Powervolt’s regulation data table – is in Section 4 of the Industrial Control Transformers pillar guide. The summary below applies those steps to 480 V A00 applications.

Step 1 – List Every 120 V Load on the Secondary

Identify every device the transformer must power simultaneously: contactor coils, relay coils, PLC power supply, I/O modules, solenoid valves, HMI panels, pilot lights, and timers. Record both steady-state (sealed) VA and inrush VA for each device from the manufacturer’s datasheet.

Step 2 – Calculate Worst-Case Simultaneous Inrush

Identify the start-up sequence where the most coils energise at once. Use Powervolt’s Method A: sum the sealed VA of all loads + sum the inrush VA of all simultaneously energising loads.

(Method B produces a slightly oversized result, which is the safer default for sizing.) Electromagnetic devices – contactors, relays, solenoids – typically energise in 20–50 ms and draw 3–10× their sealed current during that period.

Step 3 – Cross-Check Against Powervolt’s Regulation Data Table

Locate your calculated inrush VA in the table below (at 85% secondary voltage, 40% power factor — the worst-case column). Select the next standard A00 rating whose inrush VA figure is greater than or equal to your calculated value.

A00 VA RatingMax Inrush VA @ 85% Secondary, 40% PF
25 VA160 VA
50 VA270 VA
75 VA435 VA
100 VA655 VA
150 VA1,300 VA
200 VA1,975 VA
250 VA2,680 VA
300 VA3,180 VA
350 VA3,665 VA
500 VA6,300 VA
750 VA10,555 VA
1000 VA15,225 VA

Source: Powervolt Group GP Standard Series regulation data table. Full 90% and 95% columns available in the online catalogue.

Size to Inrush – Not Steady-State

The most common selection error is calculating only the steady-state load. A 100 VA transformer sized to a 100 VA continuous load will sag below 85% secondary voltage when three contactors energise simultaneously at start-up. Always base the VA selection on the inrush budget using Powervolt’s regulation data table above.

Not Sure Which VA Rating Fits Your Panel?

Powervolt Group’s engineering team provides free sizing assistance. Share your load list and we’ll specify the right A00 model – or recommend a custom configuration if needed.

→  Contact Powervolt Group Engineering →

Individual Model Pages – All 14 A00 Part Numbers

Each part-number page on powervoltgroup.com includes the full datasheet (PDF), dimensional drawings, inrush derating curves, and live pricing. All pages link back here and to the GP Standard Series catalogue page.

Low-Power Range – 25 to 150 VA

Best for indicator panels, annunciators, simple motor starters, single-PLC installations, and HMI stations.

Mid-Power Range – 200 to 500 VA

Suited to combination starter panels, VFD + PLC enclosures, multi-axis machines, and CNC machining centres.

High-Power Range – 750 to 2000 VA

For full MCC buckets, SCADA panels, robot cells, stamping lines, and central automation rooms.

A00 Series Installation Quick Reference

These are the key steps for installing an A00 model. Full installation guidance – NEC code references, grounding requirements, ventilation, and troubleshooting – is in Sections 6 and 7 of the Industrial Control Transformers pillar guide.

  1. Mount on a horizontal surface using the provided heavy-gauge steel mounting plate (4 mounting slots)
  2. Connect the primary tap terminal matching your supply – 220/440, 230/460, or 240/480 V – to the multi-tap primary terminal block
  3. Install slow-blow (time-delay) primary fuses at 200% of rated primary current; optional Powervolt fuse block kits simplify installation
  4. Ground the X1 (neutral) terminal to the panel ground bus per NEC 250.186
  5. Install secondary control-circuit fuses or a breaker at 200% of rated secondary current per NEC Articles 430 and 725
  6. Allow a minimum 25 mm clearance on all sides for natural convection cooling

For the complete wiring guide, grounding options, and first-energisation safety check, see Sections 6 and 7 of the Industrial Control Transformers pillar guide.

Order the GP Standard A00 Series from Powervolt Group

All 14 A00 models are stocked at 300 W Factory Road, Addison, IL 60101 with 1 Week standard shipment. OEM pricing contracts and volume discount programmes are available. International orders welcome.

Request a Quote – Same-Day Response

Powervolt Group responds to all quote requests within one business day. Submit your part number, quantity, and delivery requirement and our sales team will provide OEM pricing and lead time.

→  Request a Quote from Powervolt Group →

Powervolt Group Inc.   |   300 W Factory Rd, Addison, IL 60101   |   1-888-797-8658   |   (630) 628-9999   |   [email protected]   |   Mon–Fri 7:30 AM – 4:00 PM CT

GP Standard A00 Series – FAQ

Is the A00 Series suitable for 50 Hz supplies?

When a transformer designed for 60 Hz operation is used on a 50 Hz supply at the same voltage, the magnetic core actually experiences a slight increase in core flux density (not a decrease), because flux is inversely proportional to frequency.

In well-designed transformers such as the GP Standard A00 Series, this increase remains within acceptable design limits, so no derating is required. However, operation at 50 Hz can result in marginally higher magnetizing current, increased reactive power demand, and slightly greater voltage drop due to higher leakage reactance effects. These impacts are generally minor and are already considered in Powervolt’s dual-frequency design margins.

What is the correct primary tap to use for a 480 V supply?

Connect to the 240/480 V tap pair on the multi-tap primary terminal block. The A00 Group also accommodates 220/440 V and 230/460 V supplies — connect to the corresponding tap pair for your available line voltage.

Can I parallel two Standard transformers for a higher VA rating?

Not recommended. Impedance mismatches between units cause unequal current sharing and can overload the lower-impedance unit. Select the next higher standard VA rating from the A00 table instead. If your load exceeds 2000 VA, contact Powervolt Group for a custom solution.

Why choose A00 over the GP Econoline Series?

The GP Standard A00 Series covers 25–2000 VA and offers a bigger core size with Class B (130 °C) insulation — necessary for high-ambient panels and for the smallest VA sizes. The GP Econoline Series covers only 300–1500 VA and uses Class F (155 °C) insulation only. For frequent start-stop duty, or any panel requiring a VA rating below 300 VA, the A00 Series is the correct specification.  See the full three-series comparison in the pillar guide.

Is an enclosed (NEMA-rated) version available?

Yes – Powervolt Group’s GP Enclosed Series is available in NEMA 3R ratings for installations outside an existing enclosure, in washdown areas, or in dusty environments. Primary: 208–600 V. Secondary: 120/240 V. VA range: 250–2000 VA.

Where can I download the GP0025-A00 datasheet?

Each part-number page on powervoltgroup.com includes a direct PDF datasheet download. Go to powervoltgroup.com/part-details/GP0025-A00 and click “View” in the Datasheet column. Datasheets for all 14 A00 models are available on their individual part-detail pages.