Powervolt Group GP Econoline Series: Complete Guide
| Part of the Powervolt Group Industrial Control Transformers knowledge hubThis article covers the GP Econoline Series in depth. For a complete overview of all three Powervolt control transformer series, VA sizing methodology, and certifications, see the full pillar guide. |
← Back to: Industrial Control Transformers — Complete Guide
The GP Econoline Series is Powervolt Group’s cost-optimised industrial control transformer line – built for OEMs and panel builders who need 300, 750, or 1500 VA capacity without paying for the full 14-step flexibility of the GP Standard Series.
Econoline shares the same UL/cUL 5085-2 listing, IEC touch-proof terminals, and 10-year warranty as Standard – at a lower cost per unit for volume OEM applications.
The series spans 3 VA ratings – 300 VA, 750 VA, and 1500 VA – each available across multiple voltage groups, for a total of 33 part numbers.
Every unit is manufactured and 100% tested in Addison, Illinois, USA, carries UL File E47299, and is CE marked, RoHS, and REACH compliant.
| Browse & Check Price — All 33 Econoline ModelsEvery GP Econoline part number is stocked at Powervolt Group’s Addison, Illinois facility. Check live pricing, datasheets, and availability.→ Browse GP Econoline Series on powervoltgroup.com → |
Powervolt Group: 1-888-797-8658 (Toll Free) | (630) 628-9999 | [email protected]
What Defines the Econoline Series
The GP Econoline Series is built on the same electrical platform as GP Standard, but offered only in three VA ratings – 300, 750, and 1500 VA – across the full range of Powervolt voltage groups.
This narrower VA lineup allows Powervolt to manufacture Econoline units at higher volume and lower unit cost.
- VA range: 300, 750, and 1500 VA only (3 fixed ratings)
- Primary voltage: 120–600 V across 17 voltage groups
- Secondary voltage: 24–240 V, group-dependent
- Insulation class: Class F (155°C), selected to meet the requirements of most industrial control applications while maintaining cost efficiency.
- Frequency: 50/60 Hz
- Certifications: UL/cUL 5085-2 Listed (UL File E47299), CE marked, RoHS, REACH
- Standards: Exceeds NEMA ST-1, ANSI, NMBTA, JIC, IEC
- Terminals: IEC touch-proof (finger-safe)
- Construction: Copper coils, heavy-gauge steel mounting plate, high inrush current capability
- Warranty: 10 years — Powervolt Group, Addison, Illinois, USA
- Part numbering: GP[VA]-[Group]00.MXX — the .MXX suffix distinguishes Econoline from Standard Series part numbers
Need a VA rating below 300, or between the Econoline steps? See the GP Standard A00 Series Guide for the full 14-step range from 25 VA to 2000 VA, or the pillar guide for the complete three-series comparison.
| Econoline vs A00 Standard — when to choose whichGP Econoline is the right choice when your VA requirement is exactly 300, 750, or 1500 VA and budget is the primary driver. If your load calculation lands between these steps, or your project needs the widest voltage-group selection, specify the GP Standard Series instead. |
Browse GP Standard Series (25–2000 VA, 14 steps) | Browse GP Enclosed Series (NEMA 3R, 250–2000 VA)
All 33 Econoline Models at a Glance
Click any part number to go directly to its live product page on powervoltgroup.com for datasheet download, pricing, and stock status. All carry UL File E47299.
300 VA Models – Light Industrial Control
Best for combination starter panels, light automation, and mixed 24V/120V control circuits.
| Part No. | Primary Voltage | Secondary Voltage | Application |
|---|---|---|---|
| GP0300-B00.MXX | 230, 460, 575V | 95, 115V | Light industrial control, moderate VA |
| GP0300-E00.MXX | 208, 230, 460V | 115V | Combination starter panels |
| GP0300-H00.MXX | 208, 277, 380V | 120V | International voltage control panels |
| GP0300-N00.MXX | 208, 277, 380V | 120/240V | Dual-secondary control circuits |
| GP0300-Q00.MXX | 240/480V | 25, 120V | Mixed 24V/120V control loads |
| GP0300-R00.MXX | 208, 230, 460V | 24, 115V | Mixed 24V/115V control loads |
| GP0300-W00.MXX | 240, 347, 380V | 120/240V | International OEM panels |
| GP0300-KH00.MXX | 240, 480, 600V | 100, 120V | Wide-voltage 100/120V control |
750 VA Models – Mid-Size Automation
Suited to multi-relay panels, moderate motor control loads, and combination starter applications.
| Part No. | Primary Voltage | Secondary Voltage | Application |
|---|---|---|---|
| GP0750-B00.MXX | 230, 460, 575V | 95, 115V | Mid-size automation panels |
| GP0750-E00.MXX | 208, 230, 460V | 115V | Combination starter panels |
| GP0750-H00.MXX | 208, 277, 380V | 120V | International voltage control panels |
| GP0750-N00.MXX | 208, 277, 380V | 120/240V | Dual-secondary control circuits |
| GP0750-Q00.MXX | 240/480V | 25, 120V | Mixed 24V/120V control loads |
| GP0750-R00.MXX | 208, 230, 460V | 24, 115V | Mixed 24V/115V control loads |
| GP0750-W00.MXX | 240, 347, 380V | 120/240V | International OEM panels |
| GP0750-KH00.MXX | 240, 480, 600V | 100, 120V | Wide-voltage 100/120V control |
1500 VA Models – High-Load Industrial Panels
For heavy automation, large MCC-style panels, and the widest voltage-group selection in the Econoline range — 1500 VA is offered in all 17 voltage groups, while 300 and 750 VA are offered in 8.
| Part No. | Primary Voltage | Secondary Voltage | Application |
|---|---|---|---|
| GP1500-A00.MXX | 220/440, 230/460, 240/480V | 110, 115, 120V | High-load North American panels |
| GP1500-B00.MXX | 230, 460, 575V | 95, 115V | High-load mixed-voltage panels |
| GP1500-C00.MXX | 480V | 240V | High-voltage secondary control |
| GP1500-D00.MXX | 600V | 240V | Highest primary voltage, 240V secondary |
| GP1500-E00.MXX | 208, 230, 460V | 115V | Combination starter panels |
| GP1500-F00.MXX | 550, 575, 600V | 110, 115, 120V | High-voltage North American panels |
| GP1500-G00.MXX | 380, 415V | 110/220V | International dual-secondary panels |
| GP1500-H00.MXX | 208, 277, 380V | 120V | International voltage control panels |
| GP1500-M00.MXX | 240/480V | 120/240V | Dual-secondary control circuits |
| GP1500-N00.MXX | 208, 277, 380V | 120/240V | Dual-secondary control circuits |
| GP1500-P00.MXX | 277V | 240V | Single-voltage 277V input panels |
| GP1500-U00.MXX | 120/240V | 120/240V | Step-down isolation, matched voltages |
| GP1500-W00.MXX | 240, 347, 380V | 120/240V | International OEM panels |
| GP1500-Z00.MXX | 208/416V | 120/240V | High-leg delta input panels |
| GP1500-GM00.MXX | 347, 380V | 120/240V | International 347/380V panels |
| GP1500-KH00.MXX | 240, 480, 600V | 100, 120V | Wide-voltage 100/120V control |
| GP1500-PH00.MXX | 277V | 120V | Single-voltage 277V to 120V panels |
Shared Specifications – GP Econoline Series
| Specification | Value |
|---|---|
| Power rating | 300, 750, or 1500 VA (3 fixed steps) |
| Primary voltage | 120–600 V |
| Secondary voltage | 24–240 V, group-dependent |
| Frequency | 50/60 Hz |
| Insulation class | Class F (155°C), selected to meet the requirements of most industrial control applications while maintaining cost efficiency. |
| Certifications | UL/cUL 5085-2 Listed (File E47299), CE marked, RoHS, REACH |
| Standards met | Exceeds NEMA ST-1, ANSI, NMBTA, JIC, IEC |
| Terminals | IEC touch-proof (finger-safe) terminal blocks |
| Construction | Copper coils, heavy-gauge steel mounting plate |
| Fuse options | Optional input/output fuse(s); fuse block kits available on request |
| Warranty | 10 years — Powervolt Group Inc., Addison, Illinois, USA |
| Made in | USA — 100% manufactured and tested in Addison, Illinois |
Choosing the Right Econoline VA Rating
Because Econoline is only offered at 300, 750, and 1500 VA, sizing is simpler than for the 14-step Standard Series – but the underlying methodology is identical.
Step 1 – List all secondary loads
Catalogue every device the transformer will power: contactor coils, relay coils, PLC power supply, I/O modules, solenoid valves, HMI panels, and pilot lights. Record sealed (steady-state) VA and inrush VA for each from the device datasheet.
Step 2 – Calculate worst-case simultaneous inrush
Sum the sealed VA of all loads plus the inrush VA of all loads that energise simultaneously at start-up (Powervolt Method B – the safer, slightly oversized approach).
Step 3 – Round up to 300, 750, or 1500 VA
Select the next Econoline step above your calculated total. If your demand is below 300 VA, or falls in one of the intermediate steps the GP Standard Series offers (100, 150, 200, 250, or 500 VA), specify GP Standard instead for a closer fit.
| ⚠️ Three steps means less precision – check your fit carefullyUnlike the GP Standard Series’ 14 VA steps, Econoline jumps from 300 to 750 to 1500 VA. A load that calculates to 400 VA must round up to 750 VA — a 47% oversizing margin. If precise sizing matters, compare against the GP Standard A00 Series, which offers 300, 350, and 500 VA steps in between. |
| Not sure if Econoline fits your load?Powervolt Group’s engineering team can confirm whether the 300/750/1500 VA Econoline steps fit your application, or recommend the closer-fit GP Standard model.→ Contact Powervolt Group Engineering → |
Econoline Series Installation Notes
Installation follows the same procedure as the GP Standard Series. Full NEC code references, grounding requirements, and the first-energisation safety check are covered in Sections 6 and 7 of the Industrial Control Transformers pillar guide.
- Mount on a horizontal surface using the heavy-gauge steel mounting plate
- Connect the primary tap terminal matching your supply voltage for the selected voltage group
- Install slow-blow primary fuses at 200% of rated primary current; optional fuse block kits available on request
- Ground the secondary neutral terminal to the panel ground bus per NEC 250.186
- Install secondary control-circuit fuses at 200% of rated secondary current per NEC Articles 430 and 725
- Allow adequate clearance for natural convection — refer to Class F (155 °C) thermal limits if your group uses Class F insulation
Order the GP Econoline Series from Powervolt Group
All 33 Econoline part numbers are stocked at 300 W Factory Road, Addison, IL 60101 with 3-day standard shipment. OEM pricing contracts and volume discount programmes are available.
- Browse all GP Econoline models – pricing, datasheets, stock status
- GP Standard A00 Series – for VA steps between Econoline ratings
- GP Standard Series full catalogue (all voltage groups, 14 VA steps)
- Cross-Reference Tool – find Powervolt equivalents for any competitor part number
- Custom Design Form – non-standard voltage, VA, or enclosure requirements
| Request a Quote — Same-Day ResponseSubmit your Econoline part number, quantity, and delivery requirement and Powervolt Group’s sales team will respond within one business day with OEM pricing and lead time.→ Request a Quote from Powervolt Group → |
Powervolt Group Inc. | 300 W Factory Rd, Addison, IL 60101 | 1-888-797-8658 | (630) 628-9999 | [email protected] | Mon–Fri 7:30 AM – 4:00 PM CT
GP Econoline Series – FAQ
Why does Econoline only come in 3 VA ratings?
Manufacturing only 300, 750, and 1500 VA allows Powervolt Group to run higher production volumes per SKU, lowering unit cost. The GP Standard Series covers the same voltage groups with 14 intermediate VA steps for applications needing a closer match.
Does Econoline carry the same warranty as GP Standard?
Yes – both series carry Powervolt Group’s 10-year warranty and the same UL/cUL 5085-2 listing (File E47299).
What does the .MXX suffix mean in the part number?
The .MXX suffix in part numbers like GP1500-A00.MXX identifies the Econoline mounting/configuration variant, distinguishing it from the equivalent GP Standard Series part number (GP1500-A00 without the suffix).
Can I get a custom VA rating between 300 and 1500?
Powervolt Group’s Custom Design Form allows you to request a non-standard VA rating. Alternatively, the GP Standard Series already covers 100, 150, 200, 250, and 500 VA in the same voltage groups.
Related Content
- Pillar guide: Industrial Control Transformers – Complete Guide | Powervolt Group
- GP Standard A00 Series: Full guide – 14 VA steps, 25–2000 VA
- GP Enclosed Series: NEMA 3R weatherproof control transformers – 250–2000 VA
- Product catalogue: GP Econoline Series – all 33 part numbers, pricing, and stock
- Cross-reference: Find Powervolt Group equivalents for any competitor part number